APC UPS RBC4 Replacement battery
2 x CSB GP12120 F2 terminal
For BE750, BK650, BP500J/650, APC62A, SC620(i), SU620(i)NET, SUVS650(i)
GP 12120, 12V 12Ah
GP 12120 is a general purpose battery up to 5 years in standby service or more than 260 cycles at 100% discharge in cycle service.
As with all CSB batteries, all are rechargeable, highly efficient, leak proof and maintenance free.
Specification
Capacity |
12 Ah @ 20hr-rate to 1.75V per cell @ 25°C (77°F) |
Weight (kg) |
Approx. 3.67kg. (8.09 lbs.) |
Maximum Discharge current (A) |
150/180A (5sec.) |
Internal Resistance Approx. |
Approx. 16.7 mΩ |
Operating Temperature Range |
Discharge:-15℃~50℃(5°F~122°F)
Charge:-15℃~40℃(5°F~104°F)
Storage:-15℃~40℃(5°F~104°F) |
Nominal Operating Temperature Range |
25°C ± 3°C (77°F ± 5°F) |
Float charging voltage |
13.5 to 13.8 VDC/unit Average at 25°C (77°F) |
Recommended Maximum Charging current limit |
3.6 A |
Equalization and Cycle Service |
14.4 to 15.0 VDC/unit Average at 25°C (77°F) |
Self Discharge |
It should be more than 75% of the capacity that before storage after stocked for 6 months at ambient temp. 25℃ |
Terminal |
F1/F2-Faston Tab187/250 |
Container Material |
ABS(UL94-HB) & Flammability resistance of(UL94-V0) can be available upon request.
|